Поставляем Ультразвуковой датчик уровня Ultrasonic level sensor, UP56-211 - UP56-211118 - 6041658 для промышленных и гражданских объектов. Оригинальная продукция с гарантией. Подбор аналога, доставка по Москве, СПб и регионам РФ.
| Medium: | Fluids |
|---|---|
| Measurement: | Switch, Continuous |
| Limiting scanning distance: | 30 mm ... 990 mm 1) |
| Operating distance: | 30 mm ... 250 mm |
| Process pressure: | 0 bar ... 6 bar, gauge pressure |
| Process temperature: | -25 °C ... 70 °C |
| footnote | 1) At 6 bar gauge |
| Resolution: | 0.18 mm |
|---|---|
| Accuracy of sensor element: | ? 2 % 1) |
| Repeatability: | ± 0.15 % 2) |
| Response time: | ? 68 ms 3) |
| footnote | 1) 2) Of final value 3) Recovery time 32 ms ... 180 ms according to EMC EN 60947-5-7 |
| Housing material: | Stainless steel 1.4571, PBT, TPU |
|---|---|
| Process connection: | G 1 A PN 6 |
| Ultrasonic frequency: | 320 kHz |
|---|---|
| Enclosure rating: | IP 67 |
| Supply voltage: | 9 V DC ... 30 V DC 1) |
| Residual ripple: | ± 10 % |
| Power consumption: | ? 80 mA 2) |
| Time delay before availability: | ? 300 ms |
| Output signal: | 1 x PNP + 4 mA ... 20 mA / 0 V ... 10 V 3) 4) |
| Hysteresis: | 3 mm |
| Signal voltage HIGH: | Uv - 3 V |
| Electrical connection: | Round connector M12 x 1, 5-pin |
| Ultrasonic transducer: | PTFE coating, FFKM |
| footnote | 1) Reverse-polarity protected 2) At 24 V DC without output load 3) Short-circuit protected, reversible 4) Automatic switching between voltage and current outputs dependet on load 4 mA ... 20 mA: RL ? 100/ at 9 V ? UB ?20 V; RL ? 500/ at UB ? 20 V; 0 V … 10 V: RL ?100 k/at UB ? 15 V, short-circuit protected |
| Ambient temperature operation: | -25 °C ... 70 °C 1) |
|---|---|
| Ambient storage temperature: | -40 °C ... 85 °C |
| footnote | 1) Temperature compensation at -25 °C ... 50 °C, can be switched off |