| Mechanical life: | ? 50 * 1E 06 switching operations |
|---|
| Contact configuration (safety contacts): | 3 contacts NO, 1 contact NC |
|---|
| Power consumption: | 10 VA |
|---|
| Supply voltage semiconductor diagnostic outputs (A3/A4): | 24 V DC (11 V DC ... 30 V DC) |
|---|
| Measurement inputs: | L1/L2/L3 |
|---|
| Measured/motor voltage: | 690 V AC |
|---|
| For UL 508 applications only: | 600 V AC |
|---|
| Voltage threshold Uan: | 20 mV ... 400 mV, adjustable |
|---|
| Standstill time ts: | 0.2 s ... 6 s, adjustable |
|---|
| Hysteresis (for detection of running motor): | 100 % |
|---|
| Response time: | 100 ms |
|---|
| Positively guided N/C contacts: | Normally closed contact (41/42) |
|---|
| Contact type: | Relay, positively guided |
|---|
| Nominal switching voltage: | 250 V AC |
|---|
| Switching capacity in accordance with AC 15: | N/C: 2 A/230 V AC (EN 60947-5-1), N/O: 3 A/230 V AC (EN 60947-5-1) |
|---|
| Switching capacity in accordance with DC 13: | 2 A/24 V DC (EN 60947-5-1) |
|---|
| Maximum switching frequency: | 1,200 /h |
|---|
| Contact service life at 230 V / 5 A (AC) cos ? = 0.5: | ? 2 * 1E 05 switching operations |
|---|
| Semiconductor application diagnostics outputs (ON, ERR): | Electrically isolated supply via A3/A4, Imax = 100 mA (short-circuit protected), ON for Release, ERR for Error |
|---|
| Signal contacts 53/54 (normally open contact): | 3 A/250 V AC G. P. |
|---|
| Safety outputs: | Normally open contact (13/14, 23/24, 33/34) |
|---|