| Safety integrity level: | SIL3 (IEC 61508), SILCL3 (IEC 62061) 1) |
|---|
| Category: | Category 4 (EN ISO 13849) 2) |
|---|
| Performance level: | PL e (EN ISO 13849) 3) |
|---|
| B10d parameter: | 1*1E 05 switching cycles (AC-15, 230 V, I = 2 A) 2.5*1E 05 switching cycles (AC-15, 230 V, I = 1 A) 5.4*1E 05 switching cycles (DC-13, 24 V, I = 0.5 A) 1*1E 07 switching cycles (DC-13, 24 V, I ? 2 A) |
|---|
| PFHd: | 1.05 * 1E-09 |
|---|
| TM (mission time): | 20 a |
|---|
| Width: | 17.8 mm |
|---|
| Contact type: | Positively driven |
|---|
| Number of enable current contacts: | 2 |
|---|
| Maximum power consumption DC: | 3.2 W |
|---|
| Type of output: | Relay contacts |
|---|
| Rated operating current (voltage): | 3 A (230 V AC) 4 A (24 V DC) |
|---|
| Maximum switching current: | 6 A |
|---|
| Mechanical life (relay contacts): | 1*1E 07 switching cycles |
|---|
| Electrical life (relay contacts): | 1*10E 05 switching cycles, dependent upon loading, details see operating instructions |
|---|
| Enclosure rating: | IP 20 |
|---|
| Ambient operating temperature from ... to: | 0 °C ... 55 °C |
|---|
| Connection type: | Plug-in terminals |
|---|
| footnote | 1) 2) 3) If the feedback current path Y1 - Y2 (external device monitoring) is monitored using an appropriate main unit |
|---|