Features
Design: | Cylindrical |
---|---|
Thread size: | M18 x 1 |
Sensing range Sn: | 12 mm |
Assured sensing range Sa: | 8.64 mm |
Installation type: | Non-flush |
Switching frequency: | 30 Hz |
Output type: | NPN |
Output function: | Complementary |
Electrical wiring: | DC 4-wire |
Enclosure rating: | IP 67 1) |
Electrical connection: | Cable, 4-wire, 2 m 2) |
Adjustment: | Potentiometer, 270 °, Sensitivity |
footnote | 1) According to EN 60529 2) Do not bend below 0 °C |
Mechanics/electronics
Housing material: | Plastic |
---|---|
Supply voltage: | 10 V DC ... 36 V |
Residual ripple: | ? 10 % 1) |
Voltage drop: | ? 2.5 V DC 2) |
Power consumption: | ? 10 mA 3) |
Time delay before availability: | ? 100 ms |
Hysteresis: | 4 % ... 20 % |
Repeatability: | ? 5 % 4) 5) |
Temperature drift (of Sr): | ± 10 % |
EMC: | According to EN 60947-5-2 6) |
Output current Ia: | ? 200 mA |
Cable material: | PVC |
Conductor cross-section: | 0.34 mm? |
Shock and vibration resistance: | 30 g, 11 ms / 10 ... 55 Hz, 1 mm |
Ambient temperature operation: | -25 °C ... +80 °C |
Housing cap material: | PBT |
Housing length: | 79.5 mm |
Thread length: | 46.5 mm |
Tightening torque, max.: | 2.6 Nm |
footnote | 1) Of Ub 2) At Ia max 3) Without load 4) Of Sr 5) Ub and Ta constant 6) In EMC critical applications, conducted interference levels may lie in the frequency range of the oscillator. This can cause changes to the output signal.(see operating instructions) |
Reduction factors
Note: | The values are reference values which may vary |
---|---|
Metal: | 1 |
Water: | 1 |
PVC: | Ca. 0.4 |
Oil: | Ca. 0.25 |
Installation note
Remark: | Associated graphic see 'Installation' |
---|---|
A: | 18 mm |
B: | 36 mm |
C: | 18 mm |
D: | 36 mm |
E: | 24 mm |